20kV - 500 KVA Dry 3 Phase Transformer Step Up And Step Down AN Or Customized

Basic Information
Place of Origin: China
Brand Name: Pearl Electric Co.,Ltd.
Certification: KEMA, CE, CCC, ISO9001
Model Number: PEC-S, SC(B) 9-15
Minimum Order Quantity: 1 unit
Price: USD/RMB
Packaging Details: Seaworthy wooden packing
Delivery Time: 30days-50days ex-work
Payment Terms: T/T, L/C
Supply Ability: 9000 units per year
Contact Now

 20kV - 500kVA Cast Resin Dry Type Transformer , Three Phases , Two Winding , Power Distribution​
 

 
Advantages:

  1. Low loss, good effect of power conservation, efficient operation
  2. Maintenance-free, advanced process structure , strong ability of resisting short circuits
  3. Withstanding lightning impulse, inflaming retarding, damp and dust-proof, low noise.
  4. It can be capable of entering the deep load center and widely used in high-rise buildings. Especially it is suitable for buildings with strict fire resistance requirements such as flammable and combustible buildings.

 
-----WHY CHOOSE US
`Brand-name part
`Guarantee/warranty
`High reputation
`Small order is also accepted
`Experienced staff
`Prompt delivery

 
Cast Resin Dry Type Transformer, Low Noise, Low Loss and Low Partial Discharge.
 

No.ItemsUnit 
I Basic Information     
1Rated Voltage ratiokV20kV / 0.433 kV
1.01Rated CapacitykVA500
1.02Applicable Standards IEC 60076
1.03Manufacturer Pearl Electric
1.04Country of Origin China
II Electric Performance     
2.06Insullation Class Class H
2.07Temperature Rise (@40℃ ambient temperature)K125K
2.08Cooling Method AN
2.09Tapping Ranging ±2*2.5%
2.1Vector Group Dyn11
2.11Noise leveldB48
2.12Impedance%4
2.13No-load lossW1310
2.14Load Loss (@120℃)W5170
2.15Local Partial dischargepC<10PC
2.16Impulse Withstand Voltage (HV/LV)kV75/0
2.17Power Frequency Withstand Voltage
(HV/LV)
kV28/3
2.18Rated Duration of Short Circuits2
III Materials & Accessories     
3.01Core Materials Silicon Steel Sheet
3.02Winding Materials Copper conductor/foil
3.03Insulation methods HV vacuum cast / LV impregnant
3.04Main Insulation Materials Epoxy Resin
3.05Tap-changerpcsOff-load tap-changer
3.06Sensor for Temperature Alarm and TrippcsYes, contact provided
3.07Protective EnclosurepcsIP00

 
 This loading guide is based on Arrhenius’ law.
The temperature within a transformer winding varies. Certain areas in a winding are exposed
to higher temperatures than others. The material deterioration rate is highest in high
temperature areas. These areas will reach the end-point first and determine the service
reliability of the whole transformer.
 
The relation between the hot-spot temperature and the average temperature in the windings
may vary from one design to another. The formulas for the hot-spot temperature are general
and may imply an uncertainty that makes the prediction of lifetime consumption
correspondingly uncertain. Manufacturers may be able to provide more precise information on
hot-spot temperatures for their particular design.
When assessing the load capability of a transformer, the ambient temperature as a function of
the load must be taken into consideration.
 Applied Standard
GB/T10228 , GB1094.11 , IEC60076-11 , DIN42523
 
 
 20kV - 500 KVA Dry 3 Phase Transformer Step Up And Step Down AN Or Customized
 
 