Low Noise , Partial Discharge 3 Phase Distribution 10kV - 125 kVA

Basic Information
Place of Origin: China
Brand Name: Pearl Electric Co.,Ltd.
Certification: KEMA, CE, CCC, ISO9001
Model Number: PEC-S, SC(B) 9-15
Minimum Order Quantity: 1 unit
Price: USD/RMB
Packaging Details: Seaworthy wooden packing
Delivery Time: 30days-50days ex-work
Payment Terms: T/T, L/C
Supply Ability: 9000 units per year
Contact Now

 10kV - 125kVA Cast Resin Dry Type Transformer , Three Phases , Two Winding , Power Distribution​
 

 

Product characteristic:

1. It can be directly installed at the load center, which is free of maintenance and install conveniently, therefore it has low comprehensive running cost.

2. With high moisture resistance, it runs normally at the moisture and can be put into operation without being dried after outage, with low loss and local discharge capacity.

3. It has small noise, strong short circuit resistance and excellent environmental performance, and can run under severe environmental condition.

4. It is safe, fire-retardant, fireproof and environment-friendly.

 

Company situation

 

The hoisting, tooling and testing equipment is complete. Pearl Electric has passed the ISO9001-2015 international standard quality management system certification. Adopting advanced technology and high quality raw material, with first class equipment and strict processing, SC-series resin casting dry type transformer. All performance indicators of the products have reached the relevant national standards and international standards.

 

Pearl Electric's products are universally used in different industries, involving power plants, chemicals, construction, mining, metallurgy, rail transportation and so on. We do utmost to meet the needs of various users.

 

 

Cast Resin Dry Type Transformer, Low Noise, Low Loss and Low Partial Discharge.

 

No. Items Unit  
I Basic Information       
1 Rated Voltage ratio kV 10kV / 0.433 kV
1.01 Rated Capacity kVA 125
1.02 Applicable Standards   IEC 60076
1.03 Manufacturer   Pearl Electric
1.04 Country of Origin   China
II Electric Performance       
2.06 Insullation Class   Class H
2.07 Temperature Rise (@40℃ ambient temperature) K 125K
2.08 Cooling Method   AN
2.09 Tapping Ranging   ±2*2.5%
2.1 Vector Group   Dyn11
2.11 Noise level dB 48
2.12 Impedance % 4
2.13 No-load loss W 530
2.14 Load Loss (@120℃) W 1960
2.15 Local Partial discharge pC <10PC
2.16 Impulse Withstand Voltage (HV/LV) kV 75/0
2.17 Power Frequency Withstand Voltage
(HV/LV)
kV 28/3
2.18 Rated Duration of Short Circuit s 2
III Materials & Accessories       
3.01 Core Materials   Silicon Steel Sheet
3.02 Winding Materials   Copper conductor/foil
3.03 Insulation methods   HV vacuum cast / LV impregnant
3.04 Main Insulation Materials   Epoxy Resin
3.05 Tap-changer pcs Off-load tap-changer
3.06 Sensor for Temperature Alarm and Trip pcs Yes, contact provided
3.07 Protective Enclosure pcs IP00

 
 
 Applied Standard


GB/T10228 , GB1094.11 , IEC60076-11 , DIN42523
 
 