35kV - 25000 kVA Power Distribution Transformer Reducing No - load Loss

Basic Information
Place of Origin: China
Brand Name: Pearl Electric Co.,Ltd.
Certification: KEMA, CE, CCC, ISO9001
Model Number: PEO-S, S9~13,SZ11-M,SZ11
Minimum Order Quantity: 1 unit
Price: USD/RMB
Packaging Details: Seaworthy wooden packing
Delivery Time: 45-50days ex-work
Payment Terms: T/T, L/C
Supply Ability: 2.5 Million KVA/Year
Contact Now

 

35kV - 25000kVA , 3 phases , Double-column , Power Distribution Transformer , Non-exitation regulating transformer​

 

Product Advantages


Core:


The core is manufactured with high quality cold rolled grain-oriented silicon steel of high magnetic conductivity, and 45° mitring and steps overlapping structure is used for core production, enable the effectiveness of reducing no-load loss and no-load current.

HV winding:


HV winding is manufactured with high quality copper conductor, adopting optimized structure to improve electric distribution. Lightning impulse wave process is carried out for calculation and analysis, thus to improve transformer's anti-lightning impulse capability.

LVwinding:


LV winding is manufactured with high quality foil conductor, so the ampere-turn balance is excellent and the transverse magnetic flux leakage is low. The anti-short circuit capability is thus greatly improved. Oil conduit is rationally designed in the windings to increase winding's heat dispersion surface, effectively reduce temperature and improve transformer's overload capability.

 

Introduction 

 

By winding number

 

35 kV class 3-phase two-winding power transformer

 

By tap-changing

 

35 kV class on-load tap-changing power transformer

 

 

35 kV class off-load tap-changing power transformer

 

 

Insulation Structure:


The transformer adopts class-A insulation. The HV and LV windings are arranged in concentric way. Between the windings are oil-clapboard insulation structure built with paper cylinder and small oil conduit.

Tank:


The tank conservator tank type with radiator fins. 


Executed Standards:
IEC60076

 

Protective relay for on-load tap-changer

 

Contact action case Reason Solution
Trip Over speed of the oil flows into the conservator Follow the operation instruction of the protective relay.

 

Pressure release valve

 

Contact action case Reason Solution
Trip --Some valve between body and conservator is closed;
--The secondary circuit failure;
--Arc discharge;
--Short circuit
Check whether the valves between body to conservator are well opened;
Check the secondary circuit;
Do gas analysis for the air relay;
Check transformer:
--Measure the insulation resistance:
--Whether short circuit has happened; Contact with the transformer manufacturer.

 

 Refer to each corresponding instructions for installation, operation and maintenance of the outsourcing parts and standard parts.

 

If any instance, which has not been included in this manual occurs in the session of installation, operation and maintenance, please contact with us in time.

 