Epoxy Resin Casting Step Down Transformer 6.6kV - 630kVA Low Loss Energy Saving

Basic Information
Place of Origin: China
Brand Name: Pearl Electric Co.,Ltd.
Certification: KEMA, CE, CCC, ISO9001
Model Number: PEC-S, SC(B) 9-15
Minimum Order Quantity: 1 unit
Price: USD/RMB
Packaging Details: Seaworthy wooden packing
Delivery Time: 30days-50days ex-work
Payment Terms: T/T, L/C
Supply Ability: 9000 units per year
Contact Now

 6.6kV - 630kVA Cast Resin Dry Type Transformer, Three Phases, Two Winding, Power Distribution
 
General Description:
Application: for power distribution system and large industrial enterprises, etc.
Standards: IEC 60076
 
Advantages:

  1. Low loss, low noise, low partial discharge, high reliability. 
  2. Strong capability with  anti-short circuit, high anti-lightning impulse capability.
  3. HV coil is vacuum casted with epoxy resin with pressure, capabilities for better the cast without pressure.
  4. Simulating analysis being used in the core model, the resonance can be avoided and the noise is reduced. Simulation calculation and analysis of lighting impulse wave are applied to the HV Coils; anti-lighting impulse capability is improved.

 

DESIGN AND STANDARDISATION

 
All outdoor apparatus including bushing insulators and fittings shall be so designed as to avoid pockets in which water can collect.
The underside of all tanks shall be ventilated to prevent corrosion.
 
Accessible means shall be provided for the easy lubrication of all bearings and where necessary, of any mechanism or moving part. Grease lubricators shall be fitted with hexagon nipples.
All taper pins used in any mechanism shall be of the split type.
 
Joints employing a gasket material shall be so constructed that the packing is maintained under sufficient compression in all parts, so that an efficient joint can be made without the use of jointing compounds. Gasket material shall be of the minimum thickness necessary and of proven composition when operating under the environmental conditions prevailing at the Site.
 
All apparatus shall be designed to obviate the risk of accidental short-circuit due to animals, birds, and vermin. Openings in ventilated enclosures shall be so constructed to prevent the entry of vermin and insects and when located in public places insertion of any objects, for example, by children.
 

 

Cast Resin Dry Type Transformer, Low Noise, Low Loss and Low Partial Discharge.

No.ItemsUnit 
I Basic Information     
1Rated Voltage ratiokV6.6kV / 0.433 kV
1.01Rated CapacitykVA630
1.02Applicable Standards IEC 60076
1.03Manufacturer Pearl Electric
1.04Country of Origin China
II Electric Performance     
2.01Rated PowerkVA630
2.02HVkV6.6
2.03LVkV0.433
2.04FrequencyHz50
2.05Number of phase Three
2.06Insullation Class Class H
2.07Temperature Rise (@40℃ ambient temperature)K125K
2.08Cooling Method AN
2.09Tapping Ranging ±2*2.5%
2.1Vector Group Dyn11
2.11Noise leveldB48
2.12Impedance%4
2.13No-load lossW1300
2.14Load Loss (@120℃)W6800
2.15Local Partial dischargepC<10PC
2.16Impulse Withstand Voltage (HV/LV)kV75/0
2.17Power Frequency Withstand Voltage
(HV/LV)
kV28/3
2.18Rated Duration of Short Circuits2
III Materials & Accessories     
3.01Core Materials Silicon Steel Sheet
3.02Winding Materials Copper conductor/foil
3.03Insulation methods HV vacuum cast / LV impregnant
3.04Main Insulation Materials Epoxy Resin
3.05Tap-changerpcsOff-load tap-changer
3.06Sensor for Temperature Alarm and TrippcsYes, contact provided
3.07Protective EnclosurepcsIP00
3.08Temperature ControlpcsAs required.
3.09Cooling FanspcsN/A
3.10Current TransformerpcsN/A
3.11Transformer wheelpcsYes
IV OTHERS     
4.01Dimensions (L*W*H)(without enclosure)mm1430*1070*1250
4.02Total mass (without enclosure)kg1870

 
 
2 Applied Standard
GB/T10228 , GB1094.11 , IEC60076-11 , DIN42523
 
 
Epoxy Resin Casting Step Down Transformer 6.6kV - 630kVA Low Loss Energy Saving 

Contact Details
Sandy

Phone Number : 86-020-22626603

WhatsApp : 008618826241798