 10kV - Class Cast Resin Dry Type Transformer, Three Phases, Two Winding, Power Distribution

 

Introduction

 

As the professional power transformer manufacturer, Pearl Electric design and manufacture various types of dry-type power transformer. The dry-type transformer manufactured by Pearl Electric features low noise, low loss and low partial discharge. With excellent structure, superior materials, scientific design, strict production technology and advanced testing method. Product catalogues are available upon requirement.

 

 


Features & Advantages


The epoxy resin casting dry-type transformer manufactured by Pearl Electric is a type of transformer with low noise, low loss and low partial discharge. With excellent structure, superior materials, scientific design, strict production technology and advanced testing method, the transformer also has the following advantages:


1. Self-extinguishing and inflaming retarding, fire-proof and explosion-proof, pollution-free and no toxic gas being generated.


2. Excellent damp-proof performance, capable of working under 100% relative humidity and other harsh conditions, with no damp-removing measures needed.


3. Thin resin structure realizes chap-free surface and excellent heat-dispersion performance.


4. Great overload capability, capable of operating continuously under 110% overload conditions and in case of air forced cooling, operating continuously under150% overload conditions.


5. Nice appearance, small-size, less installation space occupation and low engineering cost.


6. Each performance index and technical specification excels those specified in China GB, international IEC or industrial standards.
 

 

Fire Behaviour Class


The transformer fire behaviour class shall be of Class F1 in accordance with IEC 60076-11
Clause 13.3 where the transformer when subjected to a fire hazard, restricted flammability is
required and the emission of toxic substances and opaque smoke shall be minimized.


Overloading


The transformer shall be capable of performing under temporary emergency overloading
condition up to 130% in addition to its rated power for continuous loading. Winding hot spot
temperature calculation to represent each rated power of the transformer offered under 130%
overloading for 1 hour from initial loading of 75%, according to IEC 60076-12.


Over-excitation


Under normal service conditions, the transformer shall be capable of operating in overexcitation
condition with an increased magnetic flux up to 110% of the nominal voltage.

 

Short Circuit Impedance


The short circuit impedance referred to the principal tapping at a reference temperature of
120°C shall be 4.75% with tolerance of ± 10% in accordance with IEC 60076-1.

 


Executed standards


IEC60076-11, DIN42523

 

 

About FAT test (Subject to client's requirement)

  1. Control on all transformers
  • Visual examination and verification on all transformers
  • Results of routine test examination

2.Test on sample (transformer)

 

The following tests shall be performed on sample of transformers by rating power and voltage level :

  • Conformity to the drawings
  • Temperature rise test
  • BIL test

3.Samples test

 

The number of samples shall be determined by using the ISO 2859-1 standard :

The following tests shall be performed on samples :

 