Electrical Three Phase Dry Type Transformer Insulation Class High 11-0.4kV

Basic Information
Place of Origin: China
Brand Name: Pearl Electric
Certification: KEMA, CE, CCC, ISO9001
Model Number: PEC-S, SC(B) 9-15
Minimum Order Quantity: Negotiable
Price: Negotiable
Packaging Details: Seaworthy wooden packing
Delivery Time: 30days-50days ex-work
Payment Terms: T/T, L/C
Supply Ability: 9000 units per year
Contact Now
Name: Three Phase Dry Type Transformer Cooling: Customized
Winding: Two-winding Transformer Rated H. V.: 11Kv Or Customized
Rated L. V.: 0.4kv Or Customized Insulation: Cast Resin
High Light:

air cooled transformer dry type

,

dry cast resin transformers

Electrical Three Phase Dry Type Transformer Insulation Class High 11-0.4kV
 

Three Phase Dry Type Transformer Introduction

 

Three Phase Dry Type Transformer , can be used as oil-immersed distribution transformer replacement products, all types of dry-type transformers in the best performance products, especially for urban power grids, high-rise buildings, business centers, theaters, hospitals, Hotels, tunnels, subways, underground power plants, laboratories, stations, docks, airports, combined substations and other important places.

 

Three Phase Dry Type Transformer Application

 

Dry type transformer is widely used in local lighting, high-rise buildings, airports, ports, CNC mechanical equipment and other places. We have different types of transformers, they have their own different USES.

 

Three Phase Dry Type Transformer Feature

 

Low noise, Low loss, Low temperature rise, better overload capacity, integrated intellectual interface.

 

Three Phase Dry Type Transformer Installation

 

1 Before equipment installation, please first refer to the following materials carefully: this manual, nameplate and overall dimensional drawings, thus to get familiar with the product’s total weight and installation methods and prepare corresponding lifting facility and special tools.

 

2 The transformer should be kept at least 300mm away from walls and other equipment during installation. Transformers installed side by side should have at least 300mm clearance.

 

3 The minimum safe distance between conductors and ground should conform to IEC76-3-1 POWER TRANSFORMERS-INSULATION LEVELS AND DIELECTRIC TEST-EXTERNAL CLEARANCES IN AIR.

 

4 The minimum safe distance between the HV coil and ground is listed as follows:

 

HV voltage £1kV 6kV 10kV 15kV 20kV 35kV
Net distance (mm) 40 60 90 120 160 250

 

Three Phase Dry Type Transformer Parameters

 

No. Items Unit PEC-S-kVA/HV/LV
I Basic Information       
1 Rated Voltage ratio kV 11kV / 0.433 kV
1.01 Rated Capacity kVA 2000
II Electric Performance       
2.01 Rated Power kVA 2500
2.02 HV kV 11
2.03 LV kV 0.433
2.04 Frequency Hz 50
2.05 Number of phase   Three
2.06 Insullation Class   Class H
2.07 Temperature Rise (@40℃ ambient temperature) K 125K
2.08 Cooling Method   AN
2.09 Tapping Ranging   ±2*2.5%
2.1 Vector Group   Dyn11
2.11 Noise level dB 56
2.12 Impedance % 6
2.13 No-load loss W 3950
2.14 Load Loss (@120℃) W 20000
2.15 Local Partial discharge pC <10PC
2.16 Impulse Withstand Voltage (HV/LV) kV 75/0
2.17 Power Frequency Withstand Voltage
(HV/LV)
kV 28/3
2.18 Rated Duration of Short Circuit s 2
III Materials & Accessories       
3.01 Core Materials   Silicon Steel Sheet
3.02 Winding Materials   Copper conductor/foil
3.03 Insulation methods   HV vacuum cast / LV impregnant
3.04 Main Insulation Materials   Epoxy Resin
3.05 Tap-changer pcs Off-load tap-changer

 
 
 

Electrical Three Phase Dry Type Transformer Insulation Class High 11-0.4kV

Our Service:

 

1.OEM is available.

2.Your inquiry related to our product & price will be replied within 24 hours.

3.Well-trained & experienced staff are to answer all your inquiries in English

4.Working time: 8:00am ~17:00 pm, Monday to Friday. (UTC+8)

5.Customized solution & perfect after-sale service

6. Payment: we can accept T/T, L/C.

7. For large order, engineer can be sent to your country for on-site mainternace instructions.

 

 

 

 

 

 

Contact Details
Sandy

Phone Number : 86-020-22626603

WhatsApp : +008618826241798