50 Hz Three Phase Dry Type Transformer With Mild Street Material

Basic Information
Place of Origin: China
Brand Name: Pearl Electric
Certification: KEMA, CE, CCC, ISO9001
Model Number: PEC-S, SC(B) 9-15
Minimum Order Quantity: 1 unit
Price: USD/RMB
Packaging Details: Seaworthy wooden packing
Delivery Time: 30days-50days ex-work
Payment Terms: T/T, L/C
Supply Ability: 9000 units per year
Contact Now
Name: Three Phase Dry Type Transformer Capacity: 1600KVA Or Customized
Rated H. V.: 22Kv Or Customized Rated L. V.: 0.433kv Or Customized
Material: Mild Street Material Insulation Level: H. V.: Li/AC 75/28 L. V.: 0/3
High Light:

air cooled transformer dry type

,

dry type power transformer

50 Hz Three Phase Dry Type Transformer With Mild Street Material

 

 

Features

 

MAINTENANCE

 

Regular inspections and maintenance on a transformer are important to ensure that the transformer functions properly.

 

1 Generally, if the service site is clean and dry, check the transformer annually; if the site is dusty or exposed to chemicals or fog, inspections should be made every three to six months.

 

2 To guarantee adequate ventilation and prevent deterioration of the winding insulation, accumulated dust must be removed from the insulators, and upper and lower parts of windings. Use dry and compressed air (2~5 atmosphere pressure) to blow off dust from air channels.

 

3 Check to see whether attached parts and connections are secure; whether conductors and other accessories have become rusted or corroded; or whether electric creeping or carbonization appears on insulation. If any problem is found take appropriate corrective action.

 

4 After several years of operation (maximum of five years is recommended), check the transformer by testing insulation resistance according to section 9.4 and 9.5. Normally no other tests are required.

 

 
 

No. Items Unit  
I Basic Information       
1 Rated Voltage ratio kV 22kV / 0.433 kV
1.01 Rated Capacity kVA 1250
1.02 Applicable Standards   IEC 60076
1.03 Manufacturer   Pearl Electric
1.04 Country of Origin   China
II Electric Performance       
2.01 Rated Power kVA 1500
2.02 HV kV 22
2.03 LV kV 0.433
2.04 Frequency Hz 50
2.05 Number of phase   Three
2.06 Insullation Class   Class H
2.07 Temperature Rise (@40℃ ambient temperature) K 125K
2.08 Cooling Method   AN
2.09 Tapping Ranging   ±2*2.5%
2.1 Vector Group   Dyn11
2.11 Noise level dB 55
2.12 Impedance % 6
2.13 No-load loss W 2790
2.14 Load Loss (@120℃) W 13870
2.15 Local Partial discharge pC <10PC
2.16 Impulse Withstand Voltage (HV/LV) kV 75/0
2.17 Power Frequency Withstand Voltage
(HV/LV)
kV 28/3
2.18 Rated Duration of Short Circuit s 2
III Materials & Accessories       
3.01 Core Materials   Silicon Steel Sheet
3.02 Winding Materials   Copper conductor/foil
3.03 Insulation methods   HV vacuum cast / LV impregnant
3.04 Main Insulation Materials   Epoxy Resin

 
 
2 Applied Standard
GB/T10228 , GB1094.11 , IEC60076-11 , DIN42523
 